Free PE CSE Practice Questions

15 free practice questions with detailed solutions — including fill-in-blank, multiple-select, and drag-and-drop

Want 500+ more questions?Start your free 7-day trial →

Practice Questions

1
easyMeasurement

A differential pressure flow meter measures flow rate by sensing the pressure drop across an orifice plate. The flow rate Q is related to the differential pressure ΔP by:

A.Q ∝ ΔP
B.Q ∝ √ΔP
C.Q ∝ ΔP²
D.Q is independent of ΔP
2
easyControl Systems

In a PID controller, what does the integral action primarily address?

A.Reducing oscillations
B.Eliminating steady-state error (offset)
C.Anticipating future error
D.Increasing system bandwidth
3
easyMeasurement

Which temperature sensor type generates its own voltage based on the Seebeck effect?

A.RTD
B.Thermistor
C.Thermocouple
D.Infrared pyrometer
4
easySignals

A 4–20 mA transmitter is calibrated for 0–100 psig. What current output corresponds to 50 psig?

A.10 mA
B.12 mA
C.8 mA
D.16 mA
5
easyValves

A fail-closed (air-to-open) control valve will move to which position on loss of instrument air?

A.Fully open
B.Fully closed
C.Last position held
D.50% open
6
easyMeasurementFill-in-Blank

A hydrostatic level transmitter measures liquid level in an open tank. If the liquid has a specific gravity of 0.85, and the transmitter reads 25.0 kPa, what is the liquid level? Use g = 9.81 m/s².

Your answer: m

7
mediumControl Systems

A first-order system has a transfer function G(s) = 5/(10s + 1). The time constant and steady-state gain are:

A.τ = 10 s, K = 5
B.τ = 5 s, K = 10
C.τ = 2 s, K = 50
D.τ = 10 s, K = 0.5
8
mediumSafety/SIS

Per IEC 61511, what is the required probability of failure on demand (PFD_avg) range for SIL 2?

A.≥ 10⁻² to < 10⁻¹
B.≥ 10⁻³ to < 10⁻²
C.≥ 10⁻⁴ to < 10⁻³
D.≥ 10⁻⁵ to < 10⁻⁴
9
mediumValves

A control valve with Cv = 50 passes water (SG = 1.0) with a pressure drop of 25 psi. The flow rate in GPM is most nearly:

A.150 GPM
B.250 GPM
C.200 GPM
D.350 GPM
10
mediumControl Systems

A feedback control system has the characteristic equation s³ + 4s² + 5s + 2 = 0. Using the Routh stability criterion, the system is:

A.Stable — all Routh elements positive
B.Unstable — sign change in first column
C.Marginally stable — zero in first column
D.Cannot be determined without gain
11
mediumSignals

A Wheatstone bridge has R1 = R2 = R3 = 120 Ω and R4 (strain gauge) = 120.5 Ω. With a 10 V excitation, the output voltage is most nearly:

A.10.4 mV
B.5.2 mV
C.20.8 mV
D.2.1 mV
12
mediumSafety/SISMultiple Select

Which of the following are required elements of a Safety Instrumented System (SIS) per IEC 61511? Select all that apply.

Select all that apply

A.Logic solver (safety PLC)
B.Sensor/input element
C.Final control element (e.g., shutdown valve)
D.Historian database
E.Operator HMI display
13
hardControl Systems

In a cascade control configuration, the output of the primary (master) controller becomes:

A.The setpoint of the secondary (slave) controller
B.The process variable of the secondary controller
C.The feedback signal to the primary controller
D.The direct signal to the final control element
14
hardControl Systems

A process has the open-loop transfer function G(s) = 10/[(s+1)(s+2)(s+5)]. The gain margin is most nearly:

A.7.0 dB
B.17.0 dB
C.23.5 dB
D.∞ (system is always stable)
15
hardControl SystemsDrag & Drop

Match each control action to its primary function by dragging each action to its correct description.

Items to match:

Proportional (P)
Integral (I)
Derivative (D)
Feedforward (FF)

Target slots:

Output proportional to current error magnitude
Eliminates steady-state offset by accumulating error
Anticipates future error from rate of change
Compensates for measurable disturbances before they affect the process

Solutions

1

Correct Answer: B

Step 1: Recall the orifice flow equation

From Bernoulli's equation applied across the restriction:

Q = C_d × A × √(2ΔP / ρ)

Step 2: Identify the relationship

Since C_d, A, and ρ are constants for a given installation, Q ∝ √ΔP.

This is why DP flow meters require square-root extraction to linearize the output signal.

Why not the others? Q ∝ ΔP (linear) and Q ∝ ΔP² are incorrect relationships. Q is never independent of ΔP.

2

Correct Answer: B

Step 1: Recall PID controller actions

P (Proportional) — Output proportional to current error. Cannot eliminate offset alone.

I (Integral) — Accumulates error over time. Drives steady-state error to zero.

D (Derivative) — Responds to rate of change of error. Anticipates future error.

Step 2: Answer

Integral action eliminates steady-state error (offset) by continuing to increase its output as long as any error persists.

Why not the others? Reducing oscillations is more associated with D action. Anticipating future error is D action. Increasing bandwidth is not a primary PID function.

3

Correct Answer: C

Step 1: Identify the Seebeck effect

The Seebeck effect produces a voltage (EMF) when two dissimilar metals are joined and their junctions are at different temperatures.

Step 2: Match to sensor type

A thermocouple is the only sensor that generates its own voltage — no external excitation required.

Why not the others?

• RTD — Resistance changes with temperature (requires excitation current)

• Thermistor — Resistance changes with temperature (requires excitation)

• Infrared pyrometer — Measures emitted thermal radiation (non-contact), not based on Seebeck effect

4

Correct Answer: B

Step 1: Determine the percent of span

Span = 0–100 psig. Reading = 50 psig → 50 / 100 = 50% of span.

Step 2: Apply the 4–20 mA linear scaling formula

I = 4 + (% span) × (20 − 4)

I = 4 + 0.50 × 16 = 4 + 8 = 12 mA

Quick check: 4 mA = 0%, 12 mA = 50%, 20 mA = 100%. ✓

5

Correct Answer: B

Step 1: Understand the fail action

A fail-closed (FC) valve is also called air-to-open (ATO). Air pressure pushes the valve open against a spring.

Step 2: Determine failure position

On loss of instrument air, the spring returns the valve to its fully closed position.

Why not the others?

• Fully open = fail-open (FO) / air-to-close (ATC) valve

• Last position held = requires a lock-in-place mechanism (not standard)

• 50% open = not a standard failure mode

6

Correct Answer: 3 m

Acceptable range: 2.93.1 m

Step 1: Recall the hydrostatic pressure formula

P = ρ × g × h → h = P / (ρ × g)

Step 2: Calculate density from specific gravity

ρ = SG × ρ_water = 0.85 × 1,000 kg/m³ = 850 kg/m³

Step 3: Solve for height

h = 25,000 Pa / (850 kg/m³ × 9.81 m/s²)

h = 25,000 / 8,338.5 = 3.0 m

7

Correct Answer: A

Step 1: Recall the standard first-order transfer function form

G(s) = K / (τs + 1)

Step 2: Compare with the given transfer function

G(s) = 5 / (10s + 1)

Matching terms: K (steady-state gain) = 5, τ (time constant) = 10 s.

Physical meaning: The system reaches 63.2% of its final value in 10 seconds and settles to a gain of 5 at steady state.

8

Correct Answer: B

Step 1: Recall the SIL / PFD_avg table (IEC 61511)

• SIL 1: PFD_avg ≥ 10⁻² to < 10⁻¹

• SIL 2: PFD_avg ≥ 10⁻³ to < 10⁻²

• SIL 3: PFD_avg ≥ 10⁻⁴ to < 10⁻³

• SIL 4: PFD_avg ≥ 10⁻⁵ to < 10⁻⁴

Step 2: Answer

SIL 2 requires a PFD_avg of ≥ 10⁻³ to < 10⁻² (i.e., the SIF must have a risk reduction factor of 100–1,000).

Reference: IEC 61511, Table 3 — Safety Integrity Levels.

9

Correct Answer: B

Step 1: Recall the liquid valve sizing equation

Q = C_v × √(ΔP / SG)

Step 2: Substitute values

Q = 50 × √(25 / 1.0) = 50 × √25 = 50 × 5 = 250 GPM

Reference: ISA/IEC 60534 — Control Valve Sizing, Liquid Flow.

10

Correct Answer: A

Step 1: Construct the Routh array

Characteristic equation: s³ + 4s² + 5s + 2 = 0

Row s³: | 1 | 5 |

Row s²: | 4 | 2 |

Row s¹: | (4×5 − 1×2) / 4 = 18/4 = 4.5 | 0 |

Row s⁰: | 2 |

Step 2: Check first column for sign changes

First column: 1, 4, 4.5, 2 — all positive, no sign changes.

Conclusion: The system is stable. The number of sign changes equals the number of RHP roots (zero in this case).

11

Correct Answer: A

Step 1: Recall the Wheatstone bridge output formula

V_out = V_exc × (R4/(R3 + R4) − R2/(R1 + R2))

Step 2: Substitute values

V_out = 10 × (120.5/(120 + 120.5) − 120/(120 + 120))

V_out = 10 × (120.5/240.5 − 120/240)

V_out = 10 × (0.50104 − 0.50000)

V_out = 10 × 0.00104 = 10.4 mV

Note: This small voltage is then amplified by an instrumentation amplifier for measurement.

12
Correct Answers: ABC

Step 1: Recall the three required SIS elements (IEC 61511)

A Safety Instrumented System must include all three functional subsystems:

A — Logic solver (safety PLC) ✅ — Processes inputs and determines trip action

B — Sensor/input element ✅ — Detects the hazardous condition (e.g., pressure transmitter)

C — Final control element ✅ — Takes the safe action (e.g., shutdown valve, trip relay)

Why not D and E?

• D — Historian database: Useful for diagnostics but NOT a required SIS element

• E — Operator HMI display: Important for operations but NOT part of the SIS safety function

13

Correct Answer: A

Step 1: Understand cascade control architecture

Cascade control uses two controllers: a primary (outer/master) loop and a secondary (inner/slave) loop.

Step 2: Signal flow

Primary controller output → Setpoint of the secondary controller → Secondary controller output → Final control element

The secondary loop rejects disturbances faster because it has a shorter time constant.

Why not the others?

• B — The PV of the secondary comes from its own sensor, not the primary output

• C — The feedback to the primary is its own PV measurement

• D — The primary never directly drives the final element in cascade control

14

Correct Answer: B

Step 1: Find the phase crossover frequency (ω_pc)

Set ∠G(jω) = −180°. For G(s) = 10/[(s+1)(s+2)(s+5)]:

∠G(jω) = −[arctan(ω/1) + arctan(ω/2) + arctan(ω/5)] = −180°

Solving numerically: ω_pc ≈ 3.32 rad/s.

Step 2: Calculate gain at ω_pc

|G(jω_pc)| = 10 / [√(1+3.32²) × √(4+3.32²) × √(25+3.32²)]

= 10 / [3.47 × 3.87 × 5.50] = 10 / 73.8 ≈ 0.1355

Step 3: Calculate gain margin

GM = −20 log₁₀(0.1355) = −20 × (−0.868) ≈ 17.4 dB ≈ 17 dB

Positive gain margin → system is stable with ~17 dB of margin.

15

Correct Matching:

Proportional (P)Output proportional to current error magnitude

Integral (I)Eliminates steady-state offset by accumulating error

Derivative (D)Anticipates future error from rate of change

Feedforward (FF)Compensates for measurable disturbances before they affect the process

Proportional (P) → Output proportional to current error magnitude. Provides immediate corrective action but leaves a steady-state offset.

Integral (I) → Accumulates error over time to eliminate steady-state offset. The longer the error persists, the larger the correction.

Derivative (D) → Responds to the rate of change of error, effectively anticipating future error. Provides damping but is sensitive to noise.

Feedforward (FF) → Measures disturbances directly and compensates before they affect the process variable. Unlike feedback, it acts proactively.

Ready for 500+ More Questions?

Get full access to our complete PE CSE question bank, practice exams, and adaptive learning tools.

Start Free 7-Day Trial →

No credit card required • Cancel anytime